Waffle Slab
The sophisticated equipments and machines used in the high-tech plant must be installed on the flat floor surface of neatness and smoothness for producing the products that could meet the precision criteria. The construction techniques used for the waffle slab by the company have been acquired the appreciation and positive affirmation from the clients.

Rebar Assembly and Installation of Sleeve Tubes

Access for Concrete Pouring

Concrete Pouring

Completing Profile of the Waffle slab

 

The ground levelness criteria of the waffle slab are as follows:

a. It must be less than 3mm for a single block (inside the waffle slab, using the minor beam or main beam as the partitioned range of the sleeve components that have been pre-reserved inside the ground floor.

b. The completed section of the tube-edge and the surrounding concretes must be neatly cut.

 

c. The elevation deviation of the completed section between the neighboring steel tubes should be controlled within 1mm.

The elevation deviation of the completed section of concrete slab between the tubes should be controlled within 1mm.

d. The elevation deviation of the completed section in each block (region across the two beams) should be within 3mm.

The elevation deviation of the completed section between the neighboring slabs should be controlled within 1mm.

e. For any 50mx50m block of the entire slab, the elevation deviation of the completed section should be controlled within 10mm.

f. The elevation deviation of the concrete completed section of the entire slab should be controlled within 15mm.

 

  
  
  
  
  